5. Service parts information
5-1. Compressor
Diagnosis method of compressor (If outdoor unit LED displays error, refer to troubleshooting)
Does not start up
Stops soon after starting up
Abnormal noise
↓
↓
↓
Is there open or loose con-
nection cable?
Is there open or loose con-
nection cable?
Check if vibration noise by
loose bolt or contact noise of
piping is happening.
↓
↓
↓
Check main PCB, connection
of compressor, and winding
resistance.
(Refer to the next page)
→ If there is no failure, the
defect of compressor is con-
sidered (Locked compressor
due to clogged dirt or less oil)
Is gas pipe valve open?
(Low pressure is too low)
Defective compressor can be
considered.
(due to inside dirt clogging or
broken component)
↓
↓
↓
Replace compressor.
Check if refrigerant is
leaking.
MPa
MPa
Replace compressor.
↓
↓
↓
End
Check if strainer is clogged.
(Refer to outdoor EEV or
capillary tube in this chap-
ter.)
End
↓
Check main PCB, connection of compressor and winding resis-
tance. (Refer to the next page)
→ If there is no failure, the defect of compressor can be consid-
ered. (Compression part broken or valve defective.)
↓
Replace compressor.
↓
End
5-1. Compressor
- (03-48) -
5. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General ASHG07KPCE
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 12 16 SR_CH01_AS059EG_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 07 SR_CH02_AS059EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2022 07 07 SR_CH03_AS059EG_02 ...
Page 34: ......
Page 92: ...6 2 Outdoor unit 03 58 6 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 93: ...4 CONTROL AND FUNCTIONS 2022 07 07 SR_CH04_AS059EG_02 ...
Page 125: ...5 FILED WORKING 2022 07 07 SR_CH05_AS059EG_02 ...