2-2. E: 11. Serial communication error (Serial forward transfer
error) (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
1 time flash
Economy indicator
Continuous flash
Error code
E: 11
Detective actuator Indoor unit
Main PCB
→hen the indoor unit cannot receive the serial signal
from outdoor unit more than 2 minutes after power on,
or the indoor unit cannot receive the serial signal more
than 15 seconds during normal operation.
Fan motor
Forecast of cause
Connection failure
External cause
Main PCB failure
Indoor unit fan motor failure
Check point 1. Reset the power and operate
Does error indication show again?
Check point 2. Check connection
Check any loose or removed connection line of indoor unit and outdoor unit.
Check connection condition is control unit. (If there is loose connector, open cable or mis-wiring.)
If there is an abnormal condition, correct it by referring to the installation manual or the
DESIGN
& TECHNICAL MANUAL
.
Check point 3. Check the voltage of power supply
Check the voltage of power supply
Check if AC 207 V (AC 230 V -10%) to AC 253 V (AC 230 V +10%) appears at
outdoor unit terminal L—N.
+
-
2-2. E: 11. Serial communication error (Serial forward transfer error) (Indoor unit)
- (03-6) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...