2-32. E: A3. Compressor temperature error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
10 time flash
Timer indicator
3 time flash
Economy indicator
Continuous flash
Error code
E: A3
Detective actuator Compressor temperature thermistor
Protection stop by compressor temperature ≥ 108 °C
during compressor operation generated 2 times within
24 hours.
Forecast of cause
3-way valve not opened
EEV defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Compressor temperature thermistor failure
Insufficient refrigerant
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
Check point 2. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
Check point 3. Check the outdoor unit fan and heat exchanger
•
Check for foreign object at heat exchanger
•
Check if fan can be rotated by hand.
•
Check the motor. (Refer to outdoor unit fan motor in
48.)
Check point 4. Check the compressor thermistor
The compressor temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
2-32. E: A3. Compressor temperature error (Outdoor unit)
- (03-39) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...