2-30. E: 99. 4-way valve error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
9 time flash
Timer indicator
9 time flash
Economy indicator
Continuous flash
Error code
E: 99
Detective actuator
Indoor unit
main PCB
→hen the indoor heat exchanger temperature is
compared with the room temperature, and either
following condition is detected continuously two times,
the compressor stops.
Indoor heat exchanger temp. - Room temp. > 10 °C
(Cooling or Dry operation)
Indoor heat exchanger temp. - Room temp. < -10 °C
(Heating operation)
If the same operation is repeated 5 times, the
compressor stops permanently.
Heat exchanger temperature
thermistor
Room temperature thermistor
4-way valve
Forecast of cause
Connector connection failure
Thermistor failure
Coil failure
4-way valve failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if thermistor cable is open.
Upon correcting the removed connector or mis-wiring, reset the power.
Check point 2. Check each thermistor
•
Isn’t it fallen off the holder?
•
Is there a cable pinched?
Check characteristics of room thermistor and indoor unit heat exchanger thermistor.
For the thermistor resistance value, refer to
"Thermistor resistance values"
If defective, replace the thermistor.
2-30. E: 99. 4-way valve error (Outdoor unit)
- (03-35) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...