2. Auto changeover operation
→hen the air conditioner is set to AUTO mode by remote controller, operation starts in the optimum
mode from among heating, cooling, dry and monitoring modes. During operation, the optimum mode
is automatically switched in accordance with temperature changes. The temperature can be set be-
tween 18°C and 30°C in 1.0°C steps.
• →hen operation starts, indoor fan and outdoor fan are operated for around 1 minute.
Room temperature and outdoor temperature are sensed, and the operation mode is selected in
accordance with the table below.
Room temperature
Operation mode
Tr > Ts + 2°C
Cooling
Ts + 2°C ≥ Tr ≥ Ts - 2°C
Middle zone
Tr < Ts - 2°C
Heating
Tr: Room temperature
Ts: Setting temperature
NOTE:
→hen the operation mode is middle zone, indoor unit operation mode is selected as below.
• Same operation mode is selected as outdoor unit.
If outdoor unit is operating in cooling and heating mode, indoor unit will be operated by
the same operation mode.
• Selected by outdoor temperature.
If outdoor unit is operating in other than cooling and heating mode, indoor unit will be op-
erated according to the outdoor temperature as below.
Outdoor temp.
Operation mode
25°C or more
Cooling
Less than 25°C
Heating
• →hen the compressor was stopped for 6 consecutive minutes by temperature control function af-
ter the cooling or heating mode was selected as above, operation is switched to monitoring mode
and the operation mode selection is done again.
• →hen the middle zone is selected on the predetermining of the operation mode, the operation
mode before the changing to the monitoring mode is selected.
- (04-7) -
2. Auto changeover operation
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...