1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 6.0 °C higher than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
• →hen the room temperature is within the range of +6.0 °C to - 1.0 °C of the setting temperature,
the rotation number of compressor is controlled within the range shown in the table below. Howev-
er, the maximum rotation number is limited in the range shown in the figure below based on the
indoor fan mode and the outdoor temperature.
•
Rotation number range of compressor
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASHG18KMTE
8
80
ASHG24KMTE
10
111
1-1. Cooling operation
- (04-1) -
1. Rotation number control of compressor
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for GENERAL AOHG18KMTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 03 11 SR_CH01_AS070EG_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 11 SR_CH02_AS070EG_02 ...
Page 41: ...3 TROUBLESHOOTING 2022 03 25 SR_CH03_AS070EG_01 ...
Page 44: ......
Page 103: ...4 CONTROL AND FUNCTIONS 2022 03 25 SR_CH04_AS070EG_01 ...
Page 105: ...8 8 High temperature and high pressure release control heating mode 04 29 CONTENTS continued ...
Page 106: ......
Page 137: ...5 FILED WORKING 2022 03 25 SR_CH05_AS070EG_01 ...