Fresh air control output
• You can control duct fan by synchronization with fan operation of indoor unit.
• Wire for fresh air control output is supplied with Fresh air intake kit.
•
Connection diagram
For Relay
Output voltage: DC 12 V
Permissible current: 15 mA
1
2
Indoor
unit
PCB
CN6
L*
Relay
Fuse
Power
Fan, other
Locally purchased
+
-
*: Make the distance from the PCB to the Relay unit within 10 m.
•
Operation status
Operation
Stop
12 V
0 V
Indoor unit
fan
External
output
•
Wire (External output 1)
1
2
Wire color: Red
Wire color: White