Dip switch setting
Remote controller address setting:
When operating a number of indoor units by using a wired remote controller, DIP switch setting
for assigning unit number to each indoor unit is required.
DIP switches are normally set to make the unit number 00.
Remote
controller
address
DIP switch number
Factory setting
1
2
3
4
00
OFF
OFF
OFF
OFF
♦
01
ON
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
03
ON
ON
OFF
OFF
04
OFF
OFF
ON
OFF
05
ON
OFF
ON
OFF
06
OFF
ON
ON
OFF
07
ON
ON
ON
OFF
08
OFF
OFF
OFF
ON
09
ON
OFF
OFF
ON
10
OFF
ON
OFF
ON
11
ON
ON
OFF
ON
12
OFF
OFF
ON
ON
13
ON
OFF
ON
ON
14
OFF
ON
ON
ON
15
ON
ON
ON
ON
¢
Jumper wire setting
•
Drainage function setting (JM1)
JM1
Function
Factory setting
Connect
Enable
♦
Disconnect
Disable
•
Auto louver grille setting (JM2)
When auto louver grille kit (optional parts) is attached, set the auto louver grille setting "En-
able".
JM2
Function
Factory setting
Connect
Disable
♦
Disconnect
Enable
•
Fan delay setting (JM3)
JM3
Function
Factory setting
Connect
Disable
♦
Disconnect
Enable