2-5. Floor/Ceiling type
Model name
ABYG18LVTB
ABYG22LVTA
ABYG24LVTA
Power supply
1Ø 230 V ~50 Hz
Available voltage range
198—264 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
780
980
MED
700
820
LOW
560
680
QUIET
500
540
Heating
HIGH
780
980
MED
700
820
LOW
560
680
QUIET
500
540
Type × Q'ty
Sirocco fan × 2
Motor output
W
80
Sound pressure level *
Cooling
HIGH
dB (A)
44 (Floor console)
43 (Under ceiling)
49 (Floor console)
48 (Under ceiling)
MED
41 (Floor console)
40 (Under ceiling)
45 (Floor console)
44 (Under ceiling)
LOW
35 (Floor console)
34 (Under ceiling)
41 (Floor console)
40 (Under ceiling)
QUIET
32 (Floor console)
31 (Under ceiling)
36 (Floor console)
35 (Under ceiling)
Heating
HIGH
44 (Floor console)
43 (Under ceiling)
49 (Floor console)
48 (Under ceiling)
MED
41 (Floor console)
40 (Under ceiling)
45 (Floor console)
44 (Under ceiling)
LOW
35 (Floor console)
34 (Under ceiling)
41 (Floor console)
40 (Under ceiling)
QUIET
32 (Floor console)
31 (Under ceiling)
36 (Floor console)
35 (Under ceiling)
Heat exchanger type
Dimensions (H × W × D)
mm
252 × 800 × 39.9
252 × 800 × 53.2
Fin pitch
mm
1.30
1.45
Rows × Stages
3 × 12
4 × 12
Pipe type
Copper tube
Fin type
Aluminum
Enclosure
Material
ABS
Color
White
(Approximate color of Munsell N 9.25/)
Dimensions
(H × W × D)
Net
mm
199 × 990 × 655
Gross
320 × 1,150 × 790
Weight
Net
kg
27
Gross
36
Connection
pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas
Ø12.70 (Ø1/2)
Ø15.88 (Ø5/8)
Method
Flare
Drain hose
Material
Hard PVC
Size
mm
Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Remote controller type
Wireless (Wired [option])
NOTES:
• The protective function might work when using it outside the operation range.
• *Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 8 -
2-5. Floor/Ceiling type
2. Specifications
INDOOR UNITS
SIMULTANEOUS
MULTI
INDOOR UNITS
SIMULTANEOUS
MULTI
Summary of Contents for AUYG18LVLB
Page 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Page 181: ...Part 3 SYSTEM DESIGN ...
Page 333: ...Part 4 OPTIONAL PARTS ...