![Fujitsu AUYG18LVLB Design & Technical Manual Download Page 258](http://html.mh-extra.com/html/fujitsu/auyg18lvlb/auyg18lvlb_design-and-technical-manual_2343816258.webp)
¢
System diagram
1 remote controller:
A
Indoor unit
Remote controller
2 remote controllers:
Primary
Secondary
B
C
Indoor unit
Remote controllers
A, B, C: Remote controller cable
A ≤ 500 m;B + C ≤ 500 m
¢
Electrical wiring
1 remote controller:
Remote controller
1 (Red): 12 V
2 (White): Signal
3 (Black): COM
Indoor unit
Remote
controller
1 2 3
1 2 3
2 remote controllers:
Remote controllers
1 (Red): 12 V
2 (White): Signal
3 (Black): COM
Primary
Secondary
Indoor unit
1 2 3
1 2 3
1 2 3
Remote
controller
¢
Controller combination
As for the combined usage of the controller, refer to following figures.
Good
UTY-RVNYM UTY-RNNYM
UTY-RVNYM UTY-RSNYM
Indoor unit
UTY-RVNYM
SET TEMP.
START/STOP
Indoor unit
Indoor unit
UTY-RVNYM
- 250 -
7-5. Wired remote controller (UTY-RVNYM: Optional part)
7. Remote controller