![Fujitsu AUYG18LVLB Design & Technical Manual Download Page 293](http://html.mh-extra.com/html/fujitsu/auyg18lvlb/auyg18lvlb_design-and-technical-manual_2343816293.webp)
1) Remote controller address setting
NOTES:
• Because this setting is normally done automatically when 2-wire-type wired remote controller is
installed, setting is unnecessary.
Multiple indoor units can be operated by using one wired remote controller.
Set the unit number of each indoor unit.
Function number
Setting value
Setting description
Factory setting
00
00
Unit no. 0
♦
01
Unit no. 1
02
Unit no. 2
03
Unit no. 3
04
Unit no. 4
05
Unit no. 5
06
Unit no. 6
07
Unit no. 7
08
Unit no. 8
09
Unit no. 9
10
Unit no. 10
11
Unit no. 11
12
Unit no. 12
13
Unit no. 13
14
Unit no. 14
15
Unit no. 15
NOTES:
• When connecting Polar 3-wired remote controller, set the remote controller address in the order
of 0, 1, 2, ....., and 15.
• When different type of indoor units (such as wall mounted type and cassette type, cassette type
and duct type, or other combinations) are connected using group control system, some func-
tions may no longer be available.
2) Refrigerant circuit address
Assign the same number to all of the indoor units connected to an outdoor unit.
Function number
Setting value
Refrigerant circuit address
02
00 to 15
00
01
~
14
15
- 285 -
8-6. Function details
8. Function settings
SYSTEM
DESIGN
SYSTEM
DESIGN