8-9. Simple remote controller (UTY-RSNYM)
DIP switch
SW1
Prohibited
SW2
Dual remote controller setting
SW3
°F/°C switch
SW4
Prohibited
SW5
Prohibited
SW6
Prohibited
¢
Switch location
1
2
3
4
5
6
DIP Switch
ON
OFF
¢
DIP switch setting
SW2: Dual remote controller setting
Set the remote controller SW2 according to the following table.
Number of remote controller
Primary unit
Secondary unit
Factory setting
SW2
SW2
1 (Normal)
OFF
—
♦
2 (Dual)
OFF
ON
1 2 3
1 2 3
1 2 3
Indoor unit
Remote controller cable
Primary unit
Secondary
unit
Remote controller
SW3: Switching temperature unit °F / °C
Displayed temperature unit can be switched between Fahrenheit (°F) and Celsius (°C).
SW3
Fahrenheit (°F) / Celsius (°C)
Factory setting
OFF
°C
♦
ON
°F
- 293 -
8-9. Simple remote controller (UTY-RSNYM)
8. Function settings
SYSTEM
DESIGN
SYSTEM
DESIGN