Fresh air control output
Indoor unit type
Connector
Compact cassette
CN6
Cassette
CN6
Slim duct
CN6
Duct
CN6
Floor/Ceiling
—
Ceiling
—
Signal linked to air conditioner indoor fan on can be output.
* However, signal becomes off during cold air prevention control operation.
•
Circuit diagram example
Locally purchased
Indoor unit
control PCB
Connector
1
12 V
On/Off
2
Signal
Relay
power
supply
Example: Fan
Connected unit
Example:
Relay unit
10 m*
– *: Make the distance from the PCB to the connected unit within 10 m.
– Relay spec.: Rated DC 12 V, 50 mA to less.
On
Off
Operation
Stop
Indoor fan
Output signal
•
Optional part
Indoor unit type
Part name
Model name
Compact cassette
Fresh air intake kit
UTZ-VXAA
*
Cassette
Fresh air intake kit
UTZ-VXAA
*
Slim duct
External control set
UTD-ECS5A
Duct
External control set
UTD-ECS5A
Floor/Ceiling
—
—
Ceiling
—
—
*: This wire is included in fresh air intake kit (UTZ-VXAA).
- 229 -
6-1. Indoor unit
6. External input and output
SYSTEM
DESIGN
SYSTEM
DESIGN