![Fujitsu AUYG18LVLB Design & Technical Manual Download Page 309](http://html.mh-extra.com/html/fujitsu/auyg18lvlb/auyg18lvlb_design-and-technical-manual_2343816309.webp)
¢
Installing hose
Ma
x.
1
m
Downward
Vertical
Horizontal
Bend radius is 60 mm or more
Downward gradient of 1/50 to 1/100
Part: Hose
Upward
Trap
Vertical loop
Example of wrong construction
¢
Installing pipe
Ma
x.
1
m
VP30 (O.D.38 mm) or more
Ma
x.
1
m
Gas of 1.5-2 m
Supporter
VP25
(O.D.32 mm)
or more
Locally
arrangerd pipe
Ma
x.
1
m
Rise
Air bleeding
Trap
Bad
For construct centralized drain pipe fittings, refer to the electrical wiring.
¢
Electrical wiring
Control box
Circuit board
Drain pump wire
(Connector: Blue)
Drain pump unit
Float switch wire
(Connector: Red)
Control box cover
Indoor unit
To indoor unit circuit board
- 301 -
10-1. Drain pump unit for duct type (UTZ-PX1NBA)
10. Optional parts installation
SYSTEM
DESIGN
SYSTEM
DESIGN
Summary of Contents for AUYG18LVLB
Page 151: ...Part 2 OUTDOOR UNIT SIMULTANEOUS MULTI AOYG72LRLA AOYG90LRLA ...
Page 181: ...Part 3 SYSTEM DESIGN ...
Page 333: ...Part 4 OPTIONAL PARTS ...