Auxiliary heater output
Indoor unit type
Connector
Compact cassette
—
Cassette
—
Slim duct
CN10
Duct
CN10
Floor/Ceiling
—
Ceiling
—
Signal is output from connector when indoor fan and compressor turn on under heating operation.
*Signal output performance specifications are as shown as follows:
Example:
When Set Temperature (Ts) is 22 °C
• and room temperature (Tr) increase above 12 °C, signal output is on.
• and room temperature (Tr) increase above 21 °C, signal output is off.
• and room temperature (Tr) decrease below 19 °C, signal output is on.
• and room temperature (Tr) decrease below 10 °C, signal output is off.
Off
Off
On
Tr-Ts
Tr-Ts=-1 °C
Tr-Ts=-10 °C
Tr-Ts=-3 °C
Tr-Ts=-12 °C
•
Fan delay setting (JM3)
This is used to continue indoor unit fan operation for 1 minute after thermostat "Off" in heating
mode.
1 minute delay control set by cutting jumper wire on PCB (For details, refer to
- 230 -
6-1. Indoor unit
6. External input and output
SYSTEM
DESIGN
SYSTEM
DESIGN