2-8. E: 32.X. Indoor unit main PCB error (Indoor unit)
Indicator
Indoor unit
Operation indicator
3 time flash
Timer indicator
2 time flash
Economy indicator
Continuous flash
Error code
E: 32
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Indoor unit
main PCB
→hen power is on and there is some below case.
1. →hen model information of EEPROM is incorrect.
2. →hen the access to EEPROM failed.
Forecast of cause
External cause
Defective connection of electric components
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
Check point 2. Check Indoor unit electric components
•
Check all connectors. (loose connector or incorrect wiring)
•
Check any shortage or corrosion on PCB.
Check point 3. Replace main PCB
Change main PCB.
End
Check point 1-2. Check external cause such as noise
•
Check if the ground connection is proper.
•
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
End
NOTE: EEPROM
EEPROM (Electronically Erasable and Programmable Read Only Memory) is a non-volatile
memory which keeps memorized information even if the power is turned off. It can change
the contents electronically. To change the contents, it uses higher voltage than normal, and
it cannot change a partial contents. (Rewriting shall be done upon erasing the all contents.)
There is a limit in a number of rewriting.
2-8. E: 32.↓. Indoor unit main PCB error (Indoor unit)
- (03-22) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...