5. Service parts information
5-1. Compressor
Diagnosis method of compressor (If outdoor unit LED displays error, refer to troubleshooting)
Does not start up
Stops soon after starting up
Abnormal noise
Is there open or loose con-
nection cable?
Is there open or loose con-
nection cable?
Check if vibration noise by
loose bolt or contact noise of
piping is happening.
Check main PCB, connection
of compressor, and winding
resistance.
(Refer to the next page)
If there is no failure, the
defect of compressor is con-
sidered (Locked compressor
due to clogged dirt or less oil)
Is gas pipe valve open?
(Low pressure is too low)
Defective compressor can be
considered.
(due to inside dirt clogging or
broken component)
Replace compressor.
Check if refrigerant is
leaking.
MPa
MPa
Replace compressor.
End
Check if strainer is clogged.
(Refer to outdoor EEV or
capillary tube in this chap-
ter.)
End
Check main PCB, connection of compressor and winding resis-
tance. (Refer to the next page)
If there is no failure, the defect of compressor can be consid-
ered. (Compression part broken or valve defective.)
Replace compressor.
End
5-1. Compressor
- (03-80) -
5. Service parts information
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...