1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 11 °F (6.0 °C) higher than a set temperature, the operation rotation
number of compressor will attain to maximum performance.
• If the room temperature is 2 °F (1.0 °C) lower than a set temperature, the compressor will be
stopped.
• →hen the room temperature is within the range of +11 °F (6.0 °C) to -2 °F (1.0 °C) of the setting
temperature, the rotation number of compressor is controlled within the range shown in the table
below. However, the maximum rotation number is limited in the range shown in the figure below
based on the indoor fan mode and the outdoor temperature.
•
Rotation number of compressor range
Unit: rps
Model name
Minimum frequency
Maximum frequency
ASUH18LMAS
10
63
ASUH24LMAS
10
80
1-1. Cooling operation
- (04-1) -
1. Rotation number control of compressor
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...