3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢
Fan speed
Indoor fan speed is defined as below.
Operation mode
Fan mode
Speed (rpm)
AOUH18LMAS1
AOUH24LMAS1
Heating
PO→ERFUL
1,490
1,280
HIGH
1,390
1,180
MED+
1,320
1,040
MED
1,210
900
LO→
960
770
QUIET
810
680
Cool air prevention
680
550
S-LO→
540
450
Cooling/Fan
PO→ERFUL
1,460
1,160
HIGH
1,360
1,060
MED
1,180
900
LO→
960
770
QUIET
810
680
Soft quiet
680*
1
550*
1
S-LO→
540*
2
450*
2
Dry
↓ zone: 860
J zone: 810
↓ zone: 680
J zone: 640
*1: Fan mode only
*2: Cooling mode only
¢
Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LO→, MED, HIGH while indoor unit fan
only runs.
→hen fan mode is set at AUTO, it operates on MED fan speed.
¢
Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LO→, MED, HIGH as shown in “Fan speed” above.
Airflow change over (Cooling: Auto)
When room
temperature rises
When room
temperature drops
Tr - Ts ≥ 4°F (2
°C)
HIGH mode
MED mode
LOW mode
4°F (2
°C)
> Tr - Ts ≥ 2°F (1
°C)
2°F (1
°C) > Tr - Ts
Tr - Ts ≥ 5°F (2.5
°C)
5°F (2.5
°C)
> Tr - Ts ≥ 3°F (1.5
°C)
3°F (1.5
°C) > Tr - Ts
3-1. Indoor fan control
- (04-9) -
3. Fan control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...