Auxiliary heater control by outdoor temperature 2
This control selects heat pump or external heater according to the outdoor temperature. Even when
outdoor temperature is high, the heating is performed by using both of heat pump and external
heater.
Operation
Condition
Heater on
Heater is on as shown in following diagram of heating temperature.
Heater off
•
Heater is off as shown in following diagram of heating temperature.
•
Other than heating mode
•
Error occurred
•
Forced thermostat off
• Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
• All control temperatures will shift by adjusting “Thon”.
• Outdoor temperature zone boundary A: Adjustable by function setting number 66.
•
External heater output
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts
Tr-Ts (=Thon) ≤
-0.9°F
(
-0.5°C)
•
Outdoor temperature zone
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
A: -4°F (-20°C)*
A + 3.6°F ( 2°C): -0.4°F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66
2-4. Details of function
- (05-30) -
2. External input and output
FI
EL
D
W
O
R
K
IN
G
FI
EL
D
W
O
R
K
IN
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...