2-20. E: 73.X. Heat exchanger (Middle/Outlet) temperature
thermistor error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
7 time flash
Timer indicator
3 time flash
Economy indicator
Continuous flash
Error code
E: 73
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator
Heat exchanger liquid temperature
thermistor
•
Heat exchanger liquid temperature thermistor short
or open detected
•
Heat exchanger middle temperature thermistor
short or open detected
Heat exchanger middle
temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check Point 1 : Check the connector connection and cable open
•
Connector connection state check
•
Cable open check
Check Point 2 : Check the thermistor
•
For the outdoor unit heat exchanger thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-18.
If the voltage does not appear, replace main PCB.
End
2-20. E: 73.↓. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor
unit)
- (03-35) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...