2-4. E: 18.X. External communication error (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: 18
outdoor unit
"Error code table (Outdoor unit)"
Detective actuator Indoor unit
External
communication
error
After receiving a signal from the external input and
output PCB, the same signal has not been received for
15 seconds.
Forecast of cause
Connection failure
→LAN adapter failure
Main PCB
Check point 1. Check the connection
•
Check any loose or removed connection between the main PCB to the →AN adapter.
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
•
Check the connection condition on the →LAN adapter and the main PCB (If there is loose con-
nector, open cable or mis-wiring.)
Check point 2. Replace the →LAN adapter
If check point 1 do not improve the symptom, change →LAN adapter.
Check point 3. Replace main PCB
If check point 2 do not improve the symptom, change main PCB
End
2-4. E: 18.↓. External communication error (Indoor unit)
- (03-18) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for AOUH18LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 11 01 SR_CH01_AS052EF_01 ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 11 17 SR_CH02_AS052EF_04 ...
Page 39: ...3 TROUBLESHOOTING 2021 11 17 SR_CH03_AS052EF_01 ...
Page 42: ......
Page 135: ...4 CONTROL AND FUNCTIONS 2021 11 17 SR_CH04_AS052EF_01 ...
Page 138: ......
Page 173: ...5 FILED WORKING 2021 11 17 SR_CH05_AS052EF_01 ...