Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Detective Actuators:
Indoor unit Controller PCB
Heat exchanger (MID) Thermistor
Detective details:
When Heat Ex. temperature thermistor open or short-circuit is detected.
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failuer
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Controller PCB and execute the check operation again.
DC
02-12
Trouble shooting 8
INDOOR UNIT Error Method:
Indoor Heat Ex. Thermistor Error
31.7
39.6
49.7
62.9
80.3
103.3
134.2
176.0
17.1
20.9
25.6
Resistance value (k )
Temperature (°C )
Temperature (°C )
0
40
45
50
14.1
55
5
10
1131.9
-30
804.5
-25
579.6
-20
422.9
-15
312.3
-10
233.2
-5
15
20
25
30
35
11.6
60
10.4
63
Resistance value (k )
BLACK
BLACK
1
2
CN3
1
2
Thermistor ( Pipe temp.)
Indicate or Display:
Indoor Unit :
Operation indicator: 4 time Flash
Timer indicator : 2 time Flash
Error code : [ E : 42 ]
Economy indicator: Continuous Flash
Summary of Contents for AO*G09KXCA Series
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Page 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Page 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Page 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...