5. INDOOR FAN CONTROL
The airflow setting by the remote controller can be switched in 5 steps such as AUTO, HIGH, MED,
LOW, QUIET while the indoor main fan only runs.
When Fan mode is set at (Auto), it operates on (Me) Fan Speed.
01-05
1. Fan speed
2. FAN OPERATION
( Table5 : Indoor Fan Speed )
Operation mode
Air flow mode
Speed (rpm)
Cooling/ Fan
Hi
Me+
Me
Me
Lo
Lo -
Lo
Quiet
Quiet
Dry
S-Lo
1570
Heating
Hi
Cool air prevention
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor main fan motor will run according to a room temperature,
as shown in Fig. 6.
On the other hand, if switched in [Hi ] ~ [Quiet ], the indoor main fan motor will run at a constant airflow of [COOL]
operation modes Quiet -, Lo -, Me, Hi, as shown in Table5.
( Fig.6 : Airflow change - over ( Cooling : Auto ) )
TR : Room temperature
Ts : Setting temperature
TR-Ts
1.5°C
0.5°C
2.5°C
1.5°C
Main Fan : Hi
Dual Fan : Lo
4. DRY OPERATION
Refer to the Table5.
During the dry mode operation, the fan speed setting can not be changed.
1490
1360
1300
1130
1130
980
830
610
1390
1310
1160
1100
960
1390
X zone : 960
J zone : 720
-
Main Fan
Air flow mode
Speed (rpm)
Hi
Me
Lo
Quiet
1290
Stop
1070
930
800
800
630
630
430
0
Dual Fan(Left Dual Fan)*
+
Lo
Cool air prevention
Quiet
+
TR-Ts
Main Fan : Lo
Dual Fan : Quiet
Main Fan : Quiet
Dual Fan : Quiet
Powerful
Powerful
Powerful
*Right Dual Fan is high +30rpm more than Left Dual Fan.
(Resonance correspondence)
Lo -
1050
Quiet -
830
780
Quiet -
Powerful
TR-Ts
1.5°C
0.5°C
2.5°C
1.5°C
Main Fan : Hi
Dual Fan : Lo
TR-Ts
Main Fan : Lo
Dual Fan : Quiet
Main Fan : Lo -
Dual Fan : Quiet
Dual Fan setting is ON
Dual Fan setting is OFF
( Fig 5 : Dual Fan Speed )
Summary of Contents for AO*G09KXCA Series
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Page 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Page 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Page 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...