( Fig.1 : Limit of Maximum Frequency based on Outdoor Temperature )
1. COOLING OPERATION
1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 6.0°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
minimum
frequency
maximum
frequency
15rps
63rps
Outside air Outside air
temperature drops temperature rises
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Hi
Me
Lo
Quiet
( Table 1 : Compressor Frequency Range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is b6.0°C to -1.0°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure1 based on the
fan speed mode and the outdoor temperature.
* If the room temperature is 1.0°C lower than a set temperature,
the compressor will be stopped.
A zone
63rps
32rps
26rps
17rps
B zone
63rps
32rps
26rps
17rps
C zone
52rps
32rps
26rps
17rps
D zone
39rps
26rps
22rps
17rps
E zone
39rps
26rps
17rps
15rps
F zone
39rps
26rps
17rps
15rps
Summary of Contents for AO*G09KXCA Series
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Page 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Page 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Page 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...