7. LOUVER CONTROL
01-08
1. VERTICAL LOUVER CONTROL
Each time the Vertical SET button is pressed, the air direction will change as follow:
At the biginning of AUTO or HEAT mode, they may stay on position 1 for a while for adjustment.
If the angle is set to position 5 - 8 for more than 30 minutes in COOL or DRY mode, the louver will autmatically
return to position 4.
(*Keeping the position 5 - 8 during COOL or DRY mode may cause of condensation water drops.)
After beginning of AUTO / HEAT mode operated and automatic defrosting operation time,
the air flow will be position 1.
The airflow direction setting will temporarily become 1 when the temperature of the airflow is low at the start of
HEAT mode.
At the beginning of AUTO mode, the position you cannot change the airflow direction.
(Function Range)
3. SWING OPERATION
2. HORIZONTAL LOUVER CONTROL
(Function Range)
Each time the Vertical SET button is pressed, the air direction will change as follow:
At the beginning of AUTO mode, the position you cannot change the airflow direction.
Set the automatic swing operation, Each time the SWING Button is pressd, the operation will change.
The Left/ Right swing operation will follow the direction as shown above.
The Up/ Down Swing operation range will differ by mode as follows.
Swing operation may stop temporarily when the indoor unit fan is rotating at very low speed or is stopped.
In FAN mode, the UP/ Down swing operation range of 1 5 or 5 8 is decided according the airflow
direction previously set before starting the swing operation
(Function Range)
Up/ Down Left/ Right Up/ Down/ Left/ Right Stop swing
COOL or DRY mode HEAT mode
Horizontal air flow direction louver
COOL, DRY, or FAN mode
HEAT or FAN mode
*: Default setting
*: Default setting
Summary of Contents for AO*G09KXCA Series
Page 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION WALL MOUNTED type INVERTER ...
Page 28: ...2 TROUBLESHOOTING WALL MOUNTED type INVERTER ...
Page 82: ...3 APPENDING DATA WALL MOUNTED type INVERTER ...
Page 89: ...INDOOR UNIT Main PC board Sub PC board 4 WIRING DIAGRAMS OUTDOOR UNIT 03 07 ...
Page 90: ...4 DISASSEMBLY PROCESS WALL MOUNTED type INVERTER ...
Page 110: ...Dec 2016 Printed in Japan 3 3 17 Suenaga Takatsu ku Kawasaki 213 8502 Japan ...