7-11. Unit status monitoring and the detected value indication
The wired remote controller can monitor the indoor and outdoor units' status and display the detect-
ed result as a relevant ID.
For details of the display method, refer to the Chapter of “Display Sensor Values” in the
Installation
Manual
of →ired remote controller (Touch panel).
The status can be monitored and displayed on the wired remote controller by assigning an arbitrary
ID. For available ID list, refer to the table below.
NOTE:
Operating time for each part cannot be reset when the part is replaced. Take notes of the
operating time before replacing to count the operating time of the replaced part.
Available Sensor ID
Sensor ID
Item
Unit
Remarks
00: Indoor unit
00
000
Suction temp.
01: °F or °C
00
001
Room temp.
01: °F or °C
→hen the wired remote controller
thermistor is enabled, temperature of
the wired remote controller thermistor
is displayed.
00
002
→ired remote controller detected
temp.
01: °F or °C
00
006
Heat exchanger middle temp.
01: °F or °C
00
020
Fan rotation number
03: rpm
00
051
Float switch On/Off
08: On/Off
0: Off, 1: On (→hen the water level
rises)
00
052
Drain pump On/Off
08: On/Off
0: Off, 1: On
00
080
Indoor unit total energized hours
11: h
00
081
Total filtering hours
11: h
00
082
Indoor unit fan total operation hours
11: h
00
140
Operation or Stop (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
142
Forced stop (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
143
Operation or Stop 2 (External input)
00: —
0: Off, 1: On
—: →hen the function setting 46 is
not set
NOTE:
Available only for external
input port of the indoor unit
00
155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
156
Error On/Off (External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
00
157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE:
The value is output even if
the function setting or
rotary switch is not set.
7-11. Unit status monitoring and the detected value indication
- (04-30) -
7. Various control
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
C
O
N
TR
O
L
A
N
D
FU
N
C
TI
O
N
S
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...