2-6. E: 26. Address setting error in wired remote controller
(Indoor unit)
Indicator
→ired remote
controller
Error code
E: 26
Detective actuator
→ired remote controller (2-wire)
•
→hen the address number set by auto setting and
manual setting are mixed in one remote controller
group
•
→hen the duplicated address number exists in one
remote controller group
Indoor unit controller PCB
Forecast of cause
→rong wiring of remote controller group
→rong remote controller address setting
Indoor unit main PCB failure
Remote controller failure
Check point 1. →ire installation
•
Check the wire connection in the remote controller group (For installation method, refer to in-
stallation manual)
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
Check point 2. →rong remote controller group setting
•
The given address number by auto setting (00) and the manual set number (except 00) are not
existing in one remote controller group.
•
The remote controller address setting by UI is not existing same address.
•
The duplicate address number is not existing in one remote controller group.
Check point 3. Check indoor unit main PCB
•
Check if main PCB is damaged.
•
Change main PCB and check the error after setting remote controller address.
End
2-6. E: 26. Address setting error in wired remote controller (Indoor unit)
- (03-10) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...