2-9. E: 33. Indoor unit motor electricity consumption detection
error (Indoor unit)
Indicator
→ired remote
controller
Error code
E: 33
Detective actuator Indoor unit motor electricity
consumption detection
→hen the voltage value or the current value of the motor
go beyond the limits
Forecast of cause
Fan motor failure
Main PCB failure
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
If fan or bearing is abnormal, replace it.
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
Upon the temperature coming down, restart operation.
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
03-44.)
If indoor unit fan motor is abnormal, replace it.
Check point 4. Replace main PCB
If check point 1-3 does not improve the symptom, change main PCB.
End
2-9. E: 33. Indoor unit motor electricity consumption detection error (Indoor unit)
- (03-13) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...