4-3. Outdoor unit Electronic Expansion Valve (EEV)
¢
Models: AOUH09LUAS1, AOUH12LUAS1, and AOUH18LUAS1
Check point 1. Check connections
Check connection of connector. (Loose connector or open cable)
NOTE:
For details of wiring diagram, refer to
Check point 2. Check coil of EEV
Remove connector, check each winding resistance of coil.
Read wire
Resistance value
→hite - Red
46 Ω ±4 Ω
at 68 °F (20 °C)
↔ellow - Red
Orange - Red
Blue - Red
If Resistance value is abnormal, replace EEV.
Check point 3. Check voltage from main PCB
Remove connector and check voltage (DC 12 V)
If it does not appear, replace main PCB.
Check point 4. Check noise at start up
Turn on the power and check the operation noise.
If an abnormal noise does not show, replace main PCB.
Check point 5. Check opening and closing operation of valve
→hen valve is closed, it has a temp. difference
between inlet and outlet
Pipe (In)
Pipe (Out)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot Gas
If it is open, it has no temp. difference between
inlet and outlet
Pipe (In)
Hi TEMP.
OPEN
Example : Hot Gas
Pipe (Out)
Hi TEMP.
4-3. Outdoor unit Electronic Expansion Valve (EEV)
- (03-48) -
4. Service parts information
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...