2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
→ired remote
controller
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
→hen the indoor unit cannot receive the signal from
wired remote controller more than following time during
normal operation.
•
3-wire type: 1 minute
•
2-wire type: 2.5 minutes
→ired remote control
Forecast of cause
Terminal connection abnormal
→ired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
•
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
Check Point 1-2 : Check →ired remote controller
and main PCB
•
If it is DC 12 V, remote controller is failure.
(Main PCB is normal)
– Replace remote control
•
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
– Replace main PCB
Check voltage at CN14 (terminal 1—3,
terminal 1—2) of main PCB. (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
End
Check Point 2 : →ire installation wrong remote controller group setting
•
→rong wire connection in remote controller group (Please refer to the installation manual)
•
The number of connecting indoor unit and remote controller in one remote controller group
were less than 32 units.
Check Point 2-1 : Check Indoor unit main PCB
•
Check if main PCB damage
•
Change main PCB and check the error after setting remote controller address
End
2-3. E: 12. →ired remote controller communication error (Indoor unit)
- (03-7) -
2. Troubleshooting with error code
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...