Heat exchanger temperature thermistor
Temperature °F (°C)
Resistance (kΩ)
Voltage (V)
-22.0 (-30.0)
95.58
0.24
-12.0 (-25.0)
68.90
0.32
-4.0 (-20.0)
50.31
0.43
5.0 (-15.0)
37.19
0.57
14.0 (-10.0)
27.81
0.73
23.0 (-5.0)
21.02
0.92
32.0 (0.0)
16.05
1.14
41.0 (5.0)
12.38
1.39
50.0 (10.0)
9.63
1.65
59.0 (15.0)
7.56
1.93
68.0 (20.0)
5.98
2.21
77.0 (25.0)
4.77
2.49
86.0 (30.0)
3.84
2.77
95.0 (35.0)
3.11
3.02
104.0 (40.0)
2.53
3.26
113.0 (45.0)
2.08
3.48
122.0 (50.0)
1.71
3.68
131.0 (55.0)
1.42
3.85
140.0 (60.0)
1.19
4.00
149.0 (65.0)
1.00
4.13
158.0 (70.0)
0.84
4.25
167.0 (75.0)
0.71
4.35
176.0 (80.0)
0.61
4.43
¢
Outdoor temperature thermistor
Temperature °F (°C)
Resistance (kΩ)
Voltage (V)
-22.0 (-30.0)
224.33
0.73
-12.0 (-25.0)
159.71
0.97
-4.0 (-20.0)
115.24
1.25
5.0 (-15.0)
84.21
1.56
14.0 (-10.0)
62.28
1.90
23.0 (-5.0)
46.58
2.26
32.0 (0.0)
35.21
2.61
41.0 (5.0)
26.88
2.94
50.0 (10.0)
20.72
3.25
59.0 (15.0)
16.12
3.52
68.0 (20.0)
12.64
3.76
77.0 (25.0)
10.00
3.97
86.0 (30.0)
7.97
4.14
95.0 (35.0)
6.40
4.28
104.0 (40.0)
5.18
4.41
113.0 (45.0)
4.21
4.51
122.0 (50.0)
3.45
4.59
131.0 (55.0)
2.85
4.65
5-2. Outdoor unit
- (03-56) -
5. Thermistor resistance values
TR
O
U
B
LESH
O
O
TI
N
G
TR
O
U
B
LESH
O
O
TI
N
G
Summary of Contents for ACUH09LUAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 04 02 SR_CH01_AU021EF_01 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2021 04 02 SR_CH02_AU021EF_01 ...
Page 45: ...3 TROUBLESHOOTING 2021 04 26 SR_CH03_AU021EF_01 ...
Page 48: ......
Page 105: ...4 CONTROL AND FUNCTIONS 2021 04 26 SR_CH04_AU021EF_01 ...
Page 143: ...5 FILED WORKING 2021 04 26 SR_CH05_AU021EF_01 ...