3.2 Power Supply
3-5
1
2
3
4
5
6
7
8
9
10
3.2.3 Grounding
• Independent grounding must be used for the unit.
• Use AWG20 to AWG14 wire for the grounding cable.
• Set the grounding point near the unit to reduce the length of grounding cables.
• The signal ground (SG) and frame ground (FG) are connected inside the X1 series unit.
Always ground the X1 series unit. (The level of grounding resistance should be 100
or less.)
X1 series
unit
Other
devices
X1 series
unit
Other
devices
X1 series
unit
Other
devices
Independent grounding (best)
Shared grounding (good)
Cross grounding (prohibited)
Grounding
resistance:
100
or less
Grounding
resistance:
100
or less