37
Chapter 12 SPECIFICATIONS
12.1 General Specifications
For the items not covered in this section, the specifications of the inverter apply.
Item
Specifications
Power input voltage
21.6 to 27.0 V
Input power
35 mA at maximum (24 VDC) (not included network input power)
Operating ambient temperature range
-10 to +50
°
C
Operating ambient humidity range
5 to 95% RH (There shall be no condensation.)
External dimensions
79.6 x 127 x 47.5 mm
Applicable inverter
FRENIC-Multi, ROM version: 0700 or later
12.2 DeviceNet Specifications
For the items not covered in this section, the DeviceNet Specifications Release 2.0 apply.
Item
Specifications
Network input voltage
11 to 28 V
Network power consumption
75 mA at maximum (24 VDC)
No. of nodes connected
64 at maximum (including the master)
MAC ID
0 to 63
Insulation
500 VDC (photocoupler insulation)
Transmission rate
500 kbps/250 kbps/125 kbps
Transmission rate
500 kbps
250 kbps
125 kbps
Trunk line length
100 m
250 m
500 m
Drop line length
6 m
6 m
6 m
Maximum cable length
(Trunk line: thick cable
Drop line: thin cable)
Total length of drop lines
39 m
78 m
156 m
Messages supported
1. I/O Message (Poll, Change of State)
2. Explicit Message
Vendor ID
319 (Fuji Electric Co., Ltd.)
Device type
AC drive (code: 2)
Product code
9218
Model name
OPC-E1-DEV
Applicable device profile
AC Drive
No. of input/output bytes
Selectable between 4 and 8 bytes for input and output (independently)
Applicable DeviceNet
Specifications
DeviceNet Specifications Release 2.0 Errata 5
(Certified by ODVA Japan for Conformance Test Version A-18)
Node type
Group 2 only server
Summary of Contents for FRENIC-Multi OPC-E1-DEV