36
Chapter 11 TROUBLESHOOTING
If any problem or error occurs during DeviceNet communication, follow the troubleshooting procedures given
below.
No
Phenomenon/Symptom
Probable Causes
1
None of the LEDs on the
option would light.
•
No 24 VDC power supply is connected to this option.
•
The option is faulty.
2
er4
alarm cannot be reset
(The MS LED lights in red).
•
The option is not properly mounted.
•
The option connection cable is not connected.
•
The option is faulty.
3
The NS LED lights in red.
(
er5
alarm cannot be reset.)
•
The same node address is double assigned in DeviceNet.
•
There is a mismatch in baud (data) rate.
•
The network power (24 V) is not properly supplied.
•
Cabling for DeviceNet communications is not properly done.
•
The inverter and the option have not been powered OFF and
then ON after modifying the DIP switch settings.
4
The NS LED blinks in red.
(
er5
alarm has occurred.)
•
The cable was broken during communication.
•
The I/O scan interval is too short.
5
The NS LED would not light.
•
The node address for the option is improper.
•
The cable for DeviceNet communications was broken.
6
The NS LED keeps blinking in
green and does not come to
stay on in green.
•
The master does not request a connection.
•
The I/O scan interval has been set to be too short at the start of
communication.
•
The I/O area is invalidly mapped.
•
There is no I/O connection.
7
Even though the NS LED
lights in green, the settings for
run command or speed
command cannot be
validated.
•
Neither NetCtrl nor NetRef is set to "1."
•
On the inverter, the higher-priority run command or speed
command is enabled.
•
There is a mistake in the selection of I/O Assembly Instances.
•
The inverter and the option have not been powered OFF and
then ON after modifying the o31 data.
8
Although the speed command
has been validated, the actual
speed is different from it.
•
Refer to the FRENIC-Multi Instruction Manual
(INR-SI47-1094-E), Section 6.2.1 "Motor is running abnormally."
Summary of Contents for FRENIC-Multi OPC-E1-DEV