(2) Description of I/O Data (The I/O data are in hexadecimal notation.)
Request:
Run command is OFF. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
60 00 08 07
Response:
Stopping. The inverter is ready.
70 03 00 00
Request:
Run forward command. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
61 00 08 07
Response:
The motor is running forward and accelerating. The actual speed is increasing.
74 04 ** **
Request:
Run forward command. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
61 00 08 07
Response:
Running forward. The actual speed has reached the Reference
F4 04 08 07
Request:
Run command is OFF. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
60 00 08 07
Response:
The motor is running forward and decelerating. The actual speed is decreasing.
74 05 ** **
Request:
No run command. Speed command is changed to 300 r/min (= 012Ch). The run command and
speed command via DeviceNet are enabled.
60 00 2C 01
Response: Stopping. The inverter is ready.
70 03 00 00
Request:
Run reverse command. Speed command = 300 r/min (= 012Ch). The run command and speed
command via DeviceNet are enabled.
62 00 2C 01
Response:
The motor is running backward (in the reverse direction) and accelerating. The actual speed is
increasing.
78 04 ** **
Request:
Run reverse command. Speed command = 300 r/min (= 012Ch). The run command and speed
command via DeviceNet are enabled.
62 00 2C 01
Response:
Running in the reverse direction. The actual speed has reached Reference
F8 04 2C 01
Request:
Run reverse command. Speed command is changed to 1800 r/min (= 0708h). The run
command and speed command via DeviceNet are enabled.
62 00 08 07
Response:
The motor is running backward (in the reverse direction) and accelerating. The actual speed is
increasing.
78 04 ** **
Request:
Run reverse command. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
62 00 08 07
Response: Running in the reverse direction. The actual speed has reached Reference
F8 04 08 07
Request:
Run command is OFF. Speed command = 1800 r/min (= 0708h). The run command and speed
command via DeviceNet are enabled.
60 00 08 07
Response:
The motor is running backward (in the reverse direction) and decelerating. The actual speed is
decreasing.
78 05 ** **