30
(4) AC/DC Drive object (Class 2A hex.)
This object monitors the current speed command settings and the current speed of the inverter, and configures
their related settings. It also monitors the output data issued from the inverter.
Instance Attribute
Name
Description
Value (hex.)
R/W
Data size
0
01 hex
Revision
Revision number of AC/DC
Drive object
0001 R
Word
1 03
hex AtReference Speed
arrival
00:
Stopped/
Accelerating or
decelerating
01: Speed arrival
R Byte
04 hex
NetRef
Switching speed command
source
00: Inverter
01: DeviceNet
R/W Byte
06 hex
DriveMode
Run mode. Fixed at 0.
00: Unique to vendor
R
Byte
07 hex
SpeedActual
Speed monitor (r/min)
Actual speed
R
Word
08 hex
SpeedRef
Speed command (r/min)
-32768 to 32767 r/min
R/W
Word
09 hex
CurrentActual
Output current
(in units of 0.1 A)
Output current
R
Word
11 hex
OutputVoltage
Output voltage (V)
Output voltage
R
Word
12 hex
AccelTime
Acceleration time (ms)
0 to 65535 ms
R/W
Word
13 hex
DeccelTime
Deceleration time (ms)
0 to 65535 ms
R/W
Word
14 hex
LowSpdLimit
Lower limit speed (r/min)
0 to 32767 r/min
R/W
Word
15 hex
HighSpdLimit
Maximum speed (r/min)
0 to 32767 r/min
R/W*1
Word
16
hex
SpeedScale
Change the speed scale
(r/min) all at once, as
calculated below.
SpeedScale
2
r/min
-15 to 15
(Factory default: 0)
R/W Byte
17
hex
CurrentScale
Change the current scale
(0.1 A) all at once, as
calculated below.
le
CurrentSca
2
A
0.1
-15 to 15
(Factory default: 0)
R/W Byte
1B hex
VoltageScale
Change the voltage scale (V)
all at once, as calculated
below.
le
VoltageSca
2
V
-15 to 15
(Factory default: 0)
R/W Byte
1C hex
TimeScale
Change the time scale (ms)
all at once, as calculated
below.
TimeScale
2
ms
-15 to 15
(Factory default: 0)
R/W Byte
1D hex
RefFromNet
Current speed command
source
00: Inverter
01: DeviceNet
R Byte
*1 "Read-only" while the inverter is running.