23
(4) User Defined Assembly Instance
Output (from master to this option): o31=102
User Defined Assembly Output offers a format which allows the user to freely set or modify the function
code defined by the user using the function codes o40 to o43 beforehand. Four function codes are provided
for the user to define.
Instance byte
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
0
User-defined function code 1 (write) (lower byte) (data of function code specified by o40)
1
User-defined function code 1 (write) (upper byte) (data of function code specified by o40)
2
User-defined function code 2 (write) (lower byte) (data of function code specified by o41)
3
User-defined function code 2 (write) (upper byte) (data of function code specified by o41)
4
User-defined function code 3 (write) (lower byte) (data of function code specified by o42)
5
User-defined function code 3 (write) (upper byte) (data of function code specified by o42)
6
User-defined function code 4 (write) (lower byte) (data of function code specified by o43)
102
7
User-defined function code 4 (write) (upper byte) (data of function code specified by o43)
User-defined function code 1 (write): Write data for the function code specified by o40
User-defined function code 2 (write): Write data for the function code specified by o41
User-defined function code 3 (write): Write data for the function code specified by o42
User-defined function code 4 (write): Write data for the function code specified by o43
If you assign the same function code to more than one "o" code, only the one with the smallest "o"
code number will become effective, and all the rest will be ignored (treated as "not assigned").
(For example, if the same function code is assigned to o40 and o43, o40 becomes effective and o43
does not.)
For details about configuring the inverter's function codes using o40 to o43, refer to the next page.
Input (from this option to master): o32=103
User Defined Assembly Input offers a format which allows the user to monitor the function codes defined by
the user using the function codes o48 to o51 beforehand. Four function codes are provided for the user to
define.
Instance byte
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
0
User-defined function code 1 (read) (lower byte) (data of function code specified by o48)
1
User-defined function code 1 (read) (upper byte) (data of function code specified by o48)
2
User-defined function code 2 (read) (lower byte) (data of function code specified by o49)
3
User-defined function code 2 (read) (upper byte) (data of function code specified by o49)
4
User-defined function code 3 (read) (lower byte) (data of function code specified by o50)
5
User-defined function code 3 (read) (upper byte) (data of function code specified by o50)
6
User-defined function code 4 (read) (lower byte) (data of function code specified by o51)
103
7
User-defined function code 4 (read) (upper byte) (data of function code specified by o51)
User-defined function code 1 (read): Monitored value of the function code specified by o48
User-defined function code 2 (read): Monitored value of the function code specified by o49
User-defined function code 3 (read): Monitored value e of the function code specified by o50
User-defined function code 4 (read): Monitored value of the function code specified by o51
For details about configuring the inverter's function codes using o48 to o51, refer to the next page.
Each function code defined has its own data format. For details about the data format of each code,
refer to the RS-485 Communication Use's Manual (MEH448), Chapter 5, Section 5.2 "Data Formats."