35
Chapter 10 ALARM CODE LIST
The information on alarms that have occurred in the inverter can be monitored through DeviceNet.
They are stored in the inverter's function codes M16 to M19 as listed in Table 10.1.
The communication dedicated function codes M16 to M19 store information on the current alarm code, most
recent alarm code, 2nd recent alarm code, and 3rd recent alarm code, respectively.
Table 10.1 Alarm Codes
Alarm codes
in M16 to M19
Description
Alarm codes
in M16 to M19
Description
0
No alarm
---
22
Braking resistor overheated
dbh
1
Overcurrent
(during acceleration)
0c1
23 Motor
1
overload
0l1
2
Overcurrent
(during deceleration)
0c2
24 Motor
2
overload
0l2
3
Overcurrent
(During running at constant
speed)
0c3
25 Inverter
overload
0lu
5 Ground
fault
ef
31 Memory
error
er1
6
Overvoltage
(during acceleration)
0u1
32
Keypad communications error
er2
7
Overvoltage
(during deceleration)
0u2
33 CPU
error
er3
8
Overvoltage
(during running at constant
speed (stopped))
0u3
34
Interface option
communications error
er4
10 Undervoltage
lu
35
DeviceNet communications
error
er5
11
Input phase loss
lIn
36 Operation
protection
er6
14 Fuse
blown
fus
37 Tuning
error
er7
16 Charger
circuit
fault
pbf
38
RS-485 communications error
er8
17
Heat sink overheat
0h1
46
Output phase loss
0pl
18
Alarm issued by an external
device
0h2
51
Data saving error during
undervoltage
erf
19 Inverter
overheat
0h3
53
RS-485 communications error
(option card)
erp
20
Motor protection
(PTC thermistor)
0h4
54
LSI error
(Power printed circuit board)
erh
Summary of Contents for FRENIC-Multi OPC-E1-DEV