68
Criteria for the Proper Selection of String Fuses
General
The use of string fuses in the inverter also adds fuse protection to the solar modules.
A crucial factor for the fuse protection of solar modules is the maximum short circuit current
I
sc
of the respective solar module.
Criteria for the
Proper Selection
of String Fuses
The following criteria must be fulfilled for each solar module string when using fuse protec-
tion:
-
I
N
> 1.5 x I
SC
-
I
N
< 2.0 x I
SC
-
V
N
>/= 600 V DC
-
Fuse dimensions: Diameter 10.3 x 35 - 38 mm
I
N
Nominal current rating of fuse
I
SC
Short circuit current for standard test conditions (STC) according to solar module
data sheet
V
N
Nominal voltage rating of fuse
Effects of Using
Underrated Fuses
With underrated fuses, the nominal current value may be less than the short circuit current
of the solar module.
Effect:
The fuse may trip in intensive lighting conditions.
Fuse Recommen-
dations
You should only use the following fuses, which have been tested by Fronius, to ensure
problem-free fuse protection:
-
Littelfuse KLKD fuses
-
Cooper Bussmann PV fuses
Fronius shall not be liable for any damage or other incidents resulting from the use of other
fuses. In addition, all warranty claims are forfeited.
Application Ex-
ample
e.g.: Maximum short circuit current (I
SC
) of the solar module = 5.75 A
According to the criteria for selecting the correct fuse, the fuse must have a nominal current
greater than 1.5 times the short circuit current:
5.75 A x 1.5 = 8.625 A
The fuse that should be selected according to the "Fuses" table:
KLK D 9 with 9.0 A and 600 V AC / DC
NOTE!
Only select fuses suitable for a voltage of 600 V DC.
Summary of Contents for IG Plus 100 V-1
Page 2: ...0...
Page 4: ...2...
Page 10: ...8...
Page 16: ...14...
Page 17: ...General Information...
Page 18: ......
Page 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Page 24: ...22...
Page 25: ...Installation and Startup...
Page 26: ......
Page 76: ...74 1 2 6 x 18...
Page 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Page 89: ...Operation...
Page 90: ......
Page 126: ...124...
Page 127: ...Troubleshooting and Maintenance...
Page 128: ......
Page 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Page 150: ...148...
Page 151: ...Appendix...
Page 152: ......
Page 164: ...162...
Page 165: ...163 g...
Page 167: ...165 g...