141
g
550
Jumper set incorrectly
Description
The jumper on the C-Box PC board was not reset to the ‘SMon’
position after the solar module strings were checked
Remedy
Set the jumper on the C-Box PC board to the ‘SMon’ position
551
Fuse for solar module ground is defective
Description
The fuse for the solar module ground is defective, replace the
fuse to protect the solar module.
Remedy
Insert new fuse for the solar module ground so that the solar
modules are grounded at the negative or positive pole.
Fault is rectified automatically
If this status code keeps recurring, contact your system installer
553
Phase master deactivated due to frequently occurring errors
Description
A reintegration of the power stage set into the Mix network will
be attempted at a later time.
Remedy
If status code persists: Contact a Fronius-trained service tech-
nician
558
Feature deactivated (e.g., inverter control via the Fronius Power Control Box option)
Description
A feature had to be deactivated (e.g., after component replace-
ment).
The status code is no longer displayed after the next DC discon-
nect.
Remedy
Confirm error, update firmware using Bootloader or Fronius So-
lar.update/IG Plus, if required
(The inverter will also operate problem-free without updating the
firmware)
559
"Low Voltage Ride Through" event
Description
Grid voltage parameters outside of the limits have caused a grid
voltage gap. The inverter attempts to bridge the grid voltage
gap.
Remedy
Fault is corrected automatically when grid parameters return to
normal
If this status code keeps recurring, contact your system installer
560
Power reduction due to over-frequency
Description
The inverter reduces output power due to excessive grid fre-
quency in order to stabilize the grid.
Summary of Contents for IG Plus 100 V-1
Page 2: ...0...
Page 4: ...2...
Page 10: ...8...
Page 16: ...14...
Page 17: ...General Information...
Page 18: ......
Page 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Page 24: ...22...
Page 25: ...Installation and Startup...
Page 26: ......
Page 76: ...74 1 2 6 x 18...
Page 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Page 89: ...Operation...
Page 90: ......
Page 126: ...124...
Page 127: ...Troubleshooting and Maintenance...
Page 128: ......
Page 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Page 150: ...148...
Page 151: ...Appendix...
Page 152: ......
Page 164: ...162...
Page 165: ...163 g...
Page 167: ...165 g...