130
Class 3 status
codes
Class 3 comprises status codes that may
appear during feed-in operation and that do
not cause a permanent interruption of the
operation of feeding power into the grid.
After automatic disconnection from the grid and waiting for its conditions to return to those
stipulated, your inverter will try to resume feed-in operation.
Behavior
Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy
Should the status code persist, you should contact your system
installer
109
General grid error
This error is always displayed first for grid errors. After reviewing all power stage sets, the
grid error is specified in more detail: 1x1 / 1x4 or the display remains at "109" (e.g., when
2 phases report "104" and one phase "101")
Behavior
Grid conditions are thoroughly tested and as soon as they are
again within the permissible range, the inverter will resume
feeding power into the grid.
Remedy
Check grid connections and fuses
Should the status code persist, you should contact your system
installer
301
Overcurrent (AC)
Description
Short interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
Remedy
Fault is rectified automatically
If this status code keeps recurring, contact your system installer
302
Overcurrent (DC)
Description
Short interruption of power feeding into the grid due to overcur-
rent.
The inverter returns to the startup phase.
Remedy
Fault is rectified automatically
If this status code keeps recurring, contact your system installer
303
Over-temperature buck converter
Summary of Contents for IG Plus 100 V-1
Page 2: ...0...
Page 4: ...2...
Page 10: ...8...
Page 16: ...14...
Page 17: ...General Information...
Page 18: ......
Page 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Page 24: ...22...
Page 25: ...Installation and Startup...
Page 26: ......
Page 76: ...74 1 2 6 x 18...
Page 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Page 89: ...Operation...
Page 90: ......
Page 126: ...124...
Page 127: ...Troubleshooting and Maintenance...
Page 128: ......
Page 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Page 150: ...148...
Page 151: ...Appendix...
Page 152: ......
Page 164: ...162...
Page 165: ...163 g...
Page 167: ...165 g...