CAUTION!
Danger of damaging the inverter by overload.
-
Only connect a maximum of 20 A to an individual DC terminal.
-
Connect the DC+ cable to the right connection block of the inverter's DC ter-
minals.
-
Connect the DC- cable to the left connection block of the inverter's DC termi-
nals.
-
Identify the reversed polarity with (+) and (-) according to step 10
Tightening torque of terminals:
1.2 - 1.5 Nm
IMPORTANT!
-
Set the jumper from the 'SM
ON
' position to the 'SM
OFF
' position for correct measure-
ment results
-
Check the polarity and voltage of the solar module strings: the voltage should be a
max. of 600 V, the difference between the individual solar module strings should be a
max. of 10 V.
DC-
DC+
9
DC-
DC+
DC +
DC -
DC-
DC+
DC -
DC +
DC
+
1
DC
-
2
DC -
DC +
3
4
10
SM
ON
SM
OFF
2
1
3
11
max. 600 V
12
Summary of Contents for IG Plus 100 V-1
Page 2: ...0...
Page 4: ...2...
Page 10: ...8...
Page 16: ...14...
Page 17: ...General Information...
Page 18: ......
Page 20: ...18 Safety symbols Risk of serious injury and damage due to incorrect operation...
Page 24: ...22...
Page 25: ...Installation and Startup...
Page 26: ......
Page 76: ...74 1 2 6 x 18...
Page 80: ...78 Closing Fronius IG Plus Closing Fronius IG Plus 1 1 3 2 1 1 2 3 2 4 1 3...
Page 89: ...Operation...
Page 90: ......
Page 126: ...124...
Page 127: ...Troubleshooting and Maintenance...
Page 128: ......
Page 146: ...144 Disconnect DC wire Disconnect AC wire 8 9...
Page 150: ...148...
Page 151: ...Appendix...
Page 152: ......
Page 164: ...162...
Page 165: ...163 g...
Page 167: ...165 g...