Servicing the system | 5
B1300122_en | Operating instructions Lambdamat LM 800-1000
53
Checking the combustion chamber overpressure sensor
(Pos. M
"Periodic inspection and cleaning" [
)
r
Loosen fixing screw (A) and pull the burning chamber overpressure monitor out of the
spacer tube
r
Clean the sensor with a fine cloth
r
Check that the spacer tube is clear
r
Insert the burning chamber overpressure monitor and secure loosely with fixing
screws
Cleaning the FGR blower fan
"Periodic inspection and cleaning" [
r
Mark the position of the flange
r
Loosen the screws on the flange
r
Take out the blower fan and clean the blower wheel with a brush
r
Check the seal (A) and replace if necessary
r
Replace the blower fan
Ä
Note the marking on the flange!