5 | Servicing the system
56
B1300122_en | Operating instructions Lambdamat LM 800-1000
The following minimum requirements must be met by the operator of the system for a
successful measurement:
r
Ensure there is adequate fuel
Ä
Only use fuels of high quality which meet the requirements as stipulated in the
boiler operating instructions (“Permitted fuels” chapter)
r
Ensure that there is adequate heat consumption on the day of the measurement (e.g.
storage tank must be able to take heat for the duration of the measurement)
r
There must be a suitable measuring port in the straight flue gas pipe for the
measurement. The measuring port must be twice the flue gas pipe diameter away
from the last upstream bend.
Ä
If the measuring port is not correctly positioned, the measuring result will be
distorted
5.7.1 Switch on the system
When the cleaning is complete:
r
Reassemble all dismantled components in reverse order and check for tightness and
correct installation
r
Turn on the main switch
Ä
When the control has completed the system start, the boiler is ready for operation
r
Switch the boiler on by tapping “Boiler ON”
Ä
Automatic mode is active. The heating system is controlled via the controller
according to the selected mode in automatic mode
5.7 Emissions measurement by chimney sweep or regulatory body
Various legal regulations stipulate that heating systems must be inspected periodically. In
Germany this is regulated by the First Federal Emissions Protection Ordinance
(BimSchV) in the last amended version, and in Austria by various state laws.