2.4 Permitted uses
The Froling Lambdamat is designed exclusively for heating domestic water. Only use
fuels specified in the "Permitted fuels" section.
The unit should only be operated when it is in full working order. It must be operated in
accordance with the instructions, observing safety precautions, and you should ensure
you are aware of the potential hazards. The inspection and cleaning intervals in the
operating instructions must be observed. Ensure that any faults which might impair safety
are rectified immediately.
The manufacturer or supplier is not liable for any damage resulting from non-permitted
uses.
Only original spare parts or specific alternative spare parts authorised by the
manufacturer may be used. Any kind of change or modification made to the product will
invalidate the manufacturer’s conformity with the applicable guideline(s). In such cases,
the product will need to undergo new hazard evaluation procedures by the operator. The
operator will then be fully responsible for the declaration of conformity according to the
valid guideline(s) for the product and will need to issue a corresponding declaration for
the device. This person will then assume all of the rights and responsibilities of a
manufacturer.
2.4.1 Permitted fuels
Wood chips
Description according to
EN ISO 17225-4
Description
M20
Water content max. 20%
M30
Water content max. 30%
M35
Water content max. 35%
M40
1)
Water content max. 40%
M50
1)
Water content max. 50%
P16S
Main proportion (at least 60% mass portion): 3.15 – 16 mm, max.
length of 45 mm, previously referred to as fine wood chips G30
P31S
Main proportion (at least 60% mass portion): 3.15 – 31.5 mm, max.
length of 150 mm, previously referred to as medium-sized wood
chips G50
from 400 kW:
P45S
Main proportion (at least 60% mass portion): 3.15-45 mm, max.
length of 200 mm, previously referred to as medium-sized wood
chips G50
from 400 kW:
P63
2)
Main proportion (at least 60% mass portion): 3.15–63 mm, max.
length 350 mm, previously referred to as coarse wood chips G100
1. partial load conditions only to a limited extent
2. for hydraulic feeders only
NOTICE! When using fuels with a water content of more than 35%, a power
reduction below 65% of the nominal heat output is not permissible in part-load
operation!
Note on standards
EU:
Fuel as per EN 17225 – Part 4: Wood chips class A1 / P16S-P45S