4.3.8 Temperature monitoring device in the fuel store (TMD):
Ø 6 mm
A
❒
Position the sensor plate above the transfer channel from open to closed trough
(A) and transfer the holes to the wall
❒
Drill the marked holes
- Drill diameter 6 mm
- Min. drill depth 50 mm
❒
Hammer dowel into wall and mount sensor plate
❒
Mount the housing outside the fuel store
❒
Guide the sensor through the wall at a suitable point and push it into the sensor
plate
➥
CAUTION:
Do not kink the capillary tube!
❒
Further cabling of the on-site warning device(s) according to the enclosed
installation instructions
4
Assembly
Assembling the articulated arm rotary agitator
32