FR100L&FR200L For Wire drawing machine
- 21 -
between range 3 and 4, adjust with increment 4 between 4 and 5, adjust with increment 5 above range
5.
H00.23
Wire break control mode
Units
:
Wire break determine
mode
0
:
Automatic determine
1
:
External signal
Tens
:
Wire break VFD statue
0
:
Constant running
1
:
Stop after the delay
2
:
Coast to stop
Winding:21
Unwinding:
11
Straight
line:21
×
Units
:
Wire break determine mode
0
:
Automatic determine
When feedback signal is lower than H00.26(Wire break feedback lower limit value) or bigger than
H00.27(Wire break feedback upper limit value), and continue HOO.25(Running time after wire break),
automatic determine is valid.
1
:
External signal
Digital terminal set to be 39(wire break fault),and continue H00.10, wire break is valid
Tens
:
Wire break VFD statue
0
:
Constant running
When wire break single is valid, keypad display Arn35 alarm, then continue to run
1
:
Stop after the delay
When wire break single is valid, keypad display Arn35 alarm, inverter continue to run with
frequency setting by HOO.20, and after the time setting by H00.28, inverter decelerate to stop and
report wire break fault Err35
2
:
Coast to stop
When wire break single is valid, report wire break fault Err35, and cost to stop
H00.24
Wire break determine
delay time after starting
0.0~20.0s
5.0s
△
When inverter run, after the time of H00.24, inverter start to detect wire break single
H00.25
Wire break automatic
determine time
0.0~20.0s
1.0s
△
When H00.23 setting is 0, when the feedback value of balance bar is lower than H00.26 or bigger
than H00.27, and continue the setting time, the wire break single is valid.
H00.26
Wire break feedback
lower limit value
0.0%~
Wire break feedback
upper limit value
5.0%
△
H00.27
Wire break feedback
upper limit value
Wire break feedback lower limit
value ~100.0%
95.0%
△
When H00.23 setting is 0, when balance bar is lower than H00.26 or bigger than H00.27, wire break
timing start
H00.28
Running time after wire
break
0.0~120.0s
10.0s
△
H00.29
Running frequency after
wire break
0.00~60.00Hz
5.00Hz
△
When wire break single is valid, inverter run at the frequency of HOO.29 and stop at the time of
H00.29.
H00.30
Synthesized frequency
output upper limit
Synthesized frequency output
lower limit ~100.0%
100.0%
×
H00.31
Synthesized frequency
output lower limit
-100.0%~
Synthesized
frequency output upper limit
Winding:0.0
%
Unwinding:-1
5.0%
Straight
line:0.0%
×
The two function codes is synthesized frequency limit, synthesized frequency=Roll diameter
coefficient * host(feedforward) fre PI output frequency
H00.32
Modulator function
0:Positive
Winding:0
×