FR100L&FR200L For Wire drawing machine
- 13 -
1
2: Overvoltage stall mode
2
F11.06
Overvoltage Stall
Voltage
120.0
~
150.0%
130.0%
×
F11.07
Overvoltage Stall
Mode 2 Proportion Gain
0.1
~
100.0%
3.0%
△
F11.08
Overvoltage Stall
Mode 2 Integral Time
0.000
~
1.000s
0.010s
△
F11.10
Protection action 1
Unit's
place:
Bus
undervoltage
03000
×
0:
Fault
reported
and
coast to stop
1: Stop according to the
stop mode
2: Fault reported but
continue to run
3:
Fault
protection
disabled
Ten's digit :Power input
phase
Loss (Err09)(Same as
unit's place )
Hundred's digit :Power
output
phase loss(Err10)(Same
as unit's place )
Thousand's digit:Motor
overload (Err11)(Same as
unit's place )
Ten thousand's
digit:Inverter
overload(Err11)(Same as
unit's place )
F11.11
Protection action 2
External equipment fault
(
Err13)
00000
×
0:
Fault
reported
and
coast to stop
1: Stop according to the
stop mode
2: Fault reported but
continue to run
Ten's digit: EEPROM
read/write fault (Err15)
(Same as unit's place)
Hundred's digit:
Communication overtime
error (Err18) (Same as
unit's place)
Thousand's digit: PID
feedback loss (Err19)
(Same as unit's place)
Ten thousand's digit:
Continuous running time
reached (Err20) (Same as
unit's place)
F11.12
Protection action 3
Unit's place: Module
00000
×