- 14 -
temperature detection
disconnection
(
Err24)
0:
Fault
reported
and
coast to stop
1: Stop according to the
stop mode
2: Fault reported but
continue to run
Ten's digit: Load
becoming 0 (Err25) (Same
as unit's place)
Hundred's digit:: Reserved
Thousand's
digit:
Reserved
Ten
thousand's
digit:
Reserved
F11.14
Frequency selection for
continuing to run upon fault
0:
Current
running
frequency
0
×
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
F11.15
Backup frequency upon
abnormality
0.00
~
Fmax
0.00Hz
×
F11.17
Motor overload protection
time
30.0
~
300.0s
60.0s
×
F11.18
Overload alarm
Unit's
place:
detection
option:
00
×
0: Always detect
1:
Detect
at
constant
speed only
Ten's digit : compared
object
0: Rated current of motor
1: Rated current of drive
F11.19
Overload alarm threshold
20.0
~
200.0%
130.0%
×
F11.20
Overload alarm
activated time that
exceeding threshold
0.1
~
60.0s
5.0s
×
F11.21
Inverter overheat warning
threshold
50.0
~
100.0
℃
70.0
℃
×
F11.22
Detection level of power loss
5.0
~
100.0%
20.0%
×
F11.23
Detection time of power loss
0.1
~
60.0s
5.0s
×
F11.24
Action selection at
instantaneous power failure
0: Disabled
1
×
1: Enabled
F11.25
Decel time at
instantaneous power failure
0.0
~
6000.0s
5.0s
△
F11.26
Rapid current limit
0: Disabled
0
×
1: Enabled
F11.27
Times of automatic
reset
0
~
20
0
×
F11.28
Interval of automatic
reset
0.1
~
100.0s
1.0s
×
F11.29
DO action during fault auto
reset
0: Not act
0
×
1: Act